Remote LH2-AV-02

Technical Details

  LH1-RHT-D LH1-RHT-W

General

Transmitter 3 -wire
Supply voltage 15…40 VDC
Current consumption Transmitter with current output: < 55 mA
Parameters Humidity and/or temperature
Housing material / IP ABS / IP65
Weight wall and duct versions Approx. 140 g
Sensors integrated in device Yes
Operating and measurement range 0…50 °C / 5…95 %RH
CE / EMC compatibility 2004/108/EC

Humidity measurement

Sensor < 3 %RH (10...90 %RH)
Accuracy at 23 °C ±5 K < 3 %RH (10...90 %RH
Long-term stability < 1.5 %RH per year
Response time t63 30 s (63 % of a jump 35...80 %RH) without filter

Temperature measurement

Sensor Thermistor
Temperature range 0...50 °C
Accuracy ± 0.3 °K (0...50 °C)
Response time 4 s

Outputs

Number Two analog outputs
Current 4...20 mA

How - To - Videos

ApexRemote Series Particle Counting’s Latest Technology

Quick How To: ApexRemote || How to Connect with a Mobile Device

GET A QUOTE

First Name (*)
Last Name (*)
Company Name (*)
Email (*)
Phone (*)
Address (*)
Country (*)
Primary Industry (*)
Message (*)
(*) Required Fields

The Remote LH2-AV-02 is the ideal solution for measuring air flow in cleanroom, environmental control, laminar control, HVAC and air process applications. The remote is suitable for duct mounting. 

Features:

  • Range 0…2 m/s
  • High stability and repeatability
  • Analog output (4 – 20-mA)
  • Easy mechanical installation